The PDI PowerPak 2 is the most versatile and safest PDU on the market today. Designed and engineered to meet the exact needs of our clients, the PDI PowerPak 2 PDU brings a powerful combination of flexibility and modularity.
With hundreds of possible distribution configurations, the PDI PowerPak 2 PDU is smallest power distribution unit with true front accessibility in today’s market. A patent pending 3D access window allows true front access (TFA) for service and maintenance while offering panel board and/or sub feed distribution in the main cabinet. The PDI PowerPak 2 offers up to 400kVA DOE2016 transformer and incorporates compartmentalized design in order to isolate low and high voltage components.
| Ratings | |
| kVA rating | 100–400kVA |
| Input | 3-phase, 3-wire plus ground |
| Input voltage | @ 50 Hz: 380V – 415V @ 60 Hz: 600, 480 or 208V |
| Output | 3-phase, 4-wire plus ground |
| Output voltage | @ 50 Hz: 575, 415/240, or 380/230V
@ 60 Hz: 600, 575, 480, or 208/120V 200% neutral busbar connection Listed to UL 60950-1, CSA C22.2#60950-1, UL 891, IEC 60950-1, EN 60950-1, EN 61000-6-2, EN 61000-6-4
|
| Transformers | DOE2016 transformers standard for USA. Operating efficiency: 98% or better. Copper wound construction – better conducting and more resilient than aluminum. Dual electrostatic shield – attenuates high frequency noise. Oversized 200% neutral conductor. Common mode noise protection. Transverse mode noise protection. Optional quad-wye technology solves harmonic problems by canceling the destructive triplen and non-triplen current harmonics. |
| Enclosure | NEMA 1 enclosure with removable front, side, and rear panels. Integrated two-point latch and vision panels. Flush-mounted door handle with integral locks. Advanced door catch assures positive closure. Optional floor skirts. |
| Operating conditions | Operating temperature: ambient 0°C to 40°C. Relative humidity: 0% to 95% non-condensing. Altitude ≤ 10,000 ft. 50 Hz operating range: 47-53 Hz. 60 Hz operating range: 57-63 Hz. Storage temperature: ambient -10°C to +40°C. |
| Monitoring | Option A Option B |
| Transient suppression network (TSN) | An integrated system engineered to meet ANSI/IEEE category C standards for transient voltages and surge currents. |
| Lightning arrestor/surge suppressor | Protects the insulation of the system magnetics. |
| Distribution panelboards/sub-feed breakers | Customized distribution configurations meet the demands of any facility. |
| Redundant power distribution systems | WaveStar manual dual system Dual-Input power distribution system allows for manual source selection to isolate upstream equipment and facilitate system maintenance and repair. |
| Customization | Eaton is dedicated to providing customized solutions to meet the specific requirements of your application. Contact us at +1.800.225.4838 for further information and support. |
| Eaton Service support | After your equipment has been installed, call on the Eaton Service team for 24/7 support. |